Comparison of R134a and R516A’s performance at Different Air Velocities in Two Evaporator Ejector Cooling System
    
Yazarlar (3)
Öğr. Gör. Ümit İŞKAN Yalova Üniversitesi, Türkiye
Dr. Öğr. Üyesi Mahmut Cüneyt KAHRAMAN Yalova Üniversitesi, Türkiye
Prof. Dr. Mehmet DİREK Yalova Üniversitesi, Türkiye
Makale Türü Açık Erişim Özgün Makale (Ulusal alan endekslerinde (TR Dizin, ULAKBİM) yayınlanan tam makale)
Dergi Adı Hittite Journal of Science and Engineering
Dergi ISSN 2149-2123
Dergi Tarandığı Indeksler TR DİZİN
Makale Dili İngilizce Basım Tarihi 02-2023
Cilt / Sayı / Sayfa 10 / 1 / 69–76 DOI 10.17350/HJSE19030000293
Makale Linki http://dx.doi.org/10.17350/hjse19030000293
Özet
This study aims experimentally to investigate the performance parameters of R134a and the alternative R516A refrigerant in two evaporator ejector cooling system (DEES) at different air velocities of evaporator#1. Firstly, the tests were carried out with R134a refrig- erant under steady-state conditions at different air velocities and then repeated with low GWP R516A refrigerant. As the tests were carried out with R134a, higher cooling capacity was achieved at different air velocity values. When the air velocity value was 1.1, 1.7, 2.2, and 2.7 m s-1, the COP value obtained from the tests with R134a was 1%, 2%, 5%, and 4% higher than R516A, respectively. Additionally, test results illustrate that the higher air velocity contributed to increasing performance parameters, however air velocity higher than 2.2 m s-1 had a slight effect. The study concluded that R516A performance values are slightly lower than R134a performance and can be alternatively used as a refrigerant in vapor compression refrigeration (VCR) systems.